Communication Unit DeviceNet™ Compatible
Keyence NU-DN1
Network Communication Unit NU series
Categories: Network Communication Units, Sensors
GET A PRICE
To receive a proposal, please send your request to info@sensors-trade.com and specify the required positions and company details.
Specification
Model | NU-DN1 | ||
Number of connectable sensors | 16 units max. *1 | ||
Sensor connection | Connectable sensors | Sensor amplifi ers with N-bus support *2 | |
Number of connectable units | Up to 16 units *1 | ||
Allowable passing current | Total 1200 mA max. | ||
DeviceNet™ specifi cations | Compliant functions | I/O Message (polling), Explicit Message | |
Address setting | 0 to 63 (PGM compatible) | ||
Baud rate (automatically switched) | 500 kbps? 250 kbps? 125 kbps | ||
Maximum cable length | 500 kbps | thick cable | 100 m |
thin cable | |||
250 kbps | thick cable | 250 m | |
thin cable | 100 m | ||
125 kbps | thick cable | 500 m | |
thin cable | 100 m | ||
Power voltage | 11 to 25 VDC *3 | ||
Power consumption | 1480 mW or less (at 24 V, 60 mA max.) *4 | ||
Accessories | Instruction manual, DeviceNetTM connector, End unit | ||
Weight | Approx. 65 g (including connectors) | ||
*1 Depends on the sensor amplifi ers connected. *2 “N-bus” is the name of KEYENCE's wiring-saving system for sensor amplifi ers. *3 Power to the NU-DN1 is supplied from the DeviceNetTM communication power supply. The same power is also supplied to all sensor amplifi ers connected, via the NU-DN1. *4 Exclusive of the current supplied to the sensors connected. |